IntrisingTM SDR-960-48 is one economical slim 960W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current.
SDR-960-48 is designed with a metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between - 20°C and - 70°C under air convection. It is equipped with a constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV EN60950-1, and etc.) make SDR-960-48 a very competitive power supply solution for industrial applications.'
DC Voltage |
48V |
Rated Current |
20A |
Current Rang |
0 ~ 20A |
Rated Power |
960W |
Ripple & Noise (max.) |
250mVp-p |
Peak Current |
26A |
Peak Power |
1248W (3sec.) |
Voltage ADJ.Range |
48 ~ 55V |
Voltage Tolerance |
±1.0% |
Line Regulation |
±0.5% |
Load Regulation |
±1.0% |
Setup, Rise Time |
1000ms, 100ms / 230VAC at full load |
Hold Up Time (Typ.) |
14ms / 230VAC at full load |
Voltage Range |
90 ~ 264VAC 127 ~ 370VDC |
Frequency Range |
47 ~ 63Hz |
Efficiency (Typ.) |
12V: 85.5%24V: 88%48V: 89% |
Power Factor (Typ.) |
PF>0.98 / 115VAC, PF>0.94 / 230VAC at full load |
AC Current (Typ.) |
1.45A / 115VAC 0.9A / 230VAC |
Inrush Current (Typ.) |
20A / 115VAC 35A / 230VAC |
Leakage Current |
<1mA / 240VAC |
DC OK Relay Contact Ratings (max.) |
60Vdc / 0.3A, 30Vdc / 1A, 30Vac / 0.5A resistive load |
Current Sharing |
Please refer to function manual |
Overload |
Normally works within 105 ~ 130% rated output power for more than 3 seconds and then shut down o / p voltage with auto-recovery after 30 seconds if the peak load condition is removed.Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shut down o / p voltage, re-power on to recover |
Over Voltage |
56 ~ 65V |
Over Temperature |
Shut down o / p voltage, recovers automatically after temperature goes down |
MTBF |
69.8K hrs min. MIL-HDBK-217F (25 ) °C |
Dimension |
110 (W) x 125.2 (H) x 150mm (D) |
Weight |
2.47Kg ; 6pcs / 15.8Kg / 1.55CUFT |
Working Temp. |
-30 ~ +70°C (Refer to "Derating Curve") |
Working Humidity |
20 ~ 95% RH non-condensing |
Storage Temp., Humidity |
-40 ~ +85°C, 10 ~ 95% RH |
Temp. Coefficient |
±0.03%/°C (0 ~ 50°C) |
Vibration |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
Safety Standards |
Ul508, TUV EN60950-1 approved;(meet EN60204-1) |
Withstand Voltage |
I / P-O / P:3KVAC I / P-FG:2KVAC O / P-FG:0.5KVAC |
Isolation Resistance |
I / P-O / P, I / P-FG, O / P-FG:>100M Ohms / 500VDC / 25°C/ 70% RH |
EMC Emission |
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 |
EMC Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A |